14.14 AIR CONDITIONING SYSTEM

For further information, please contact the RIVA Service Department.


AFTER-SALES SERVICE BROCHURE


Problem Cause Corrective action
1. High crankcase temperature Overheating
Check coolant charge
Poor circulation of treated water (winter cycle) or condensation water (summer cycle) Correct circulation
2. Low suction pressure Low coolant charge Add
Poor circulation of condensation water (winter cycle) or treated water (summer cycle) Correct circulation
3. System noisy Loose fastening bolts Tighten bolts
Unit base improperly insulated Insulate foundation
Improper support or insulation of piping Use correct piping techniques and support piping with suitable hangers
Piping vibrations Clip pipes correctly. Check the couplings
4. Compressor does not start Power off Check the supply. Check fuses and/or magneto-thermal switches
Thermostat misadjusted Adjust thermostat
Pressure switch open Reset switch and check proper calibration, 20 bar (h.p.) and 2.5 bar (I.p.)
Faulty wiring Check diagram and rewire
Pumps not operating Check pumps free rotation.
Check the magneto-thermal switches
Flow-switch does not close Restore correct treated water circulation
Gas discharging unit Check coolant circuit for possible breaks due to transport and installation
5. Compressor cycles intermittently Low pressure switch erratic in operation Check pressure switch setting. Check good circulation of condensed water
Low coolant charge Add
Internal protection tripped Check for any voltage drop, correct
6. High delivery pressure with compressor stop (high pressure switch). Coolant overcharge Remove excess coolant
Insufficient or no condenser water flow; clogged condenser or sea-water strainer Adjust water regulating valve to condenser; clean condenser or sea-water strainer
Condensed water pump off Check pump and start
Poor treated water circulation (winter cycle) Check for air in the circuit
Check for possible clogging
Air in coolant circuit Restore vacuum and refill with coolant