Maintenance and check
Purge frequency or the replacement of the filter element (1) are determined by the contamination level of the fuel.
Water drain from collection tank
Check or drain the water collection tank (2) daily.
he collecting tank must be drained before polluting agents reach the turbine end.
If the engine has to carry on running, select the filter to be left in line and carry out maintenance on the other one.
This operation is a good procedure even if the engine is not running.
Replacement of filter element
Replace the element according to the time intervals recommended by the Manufacturer or if a power lack is noticed, which indicates namely that the element is clogged.
The current value varies according to the different fuel systems. Also extra elements like a tank too full or fuel excessively polluted can clog the filter.
At least once a month check the operation. At least once a week, and anyway before each refuelling, check for the presence of water in the fuel. If necessary drain the water present. When necessary, but at least once a year, replace the cartridge of the filters.
Troubleshooting procedure
The main reason for a poor start-up or lack of power is the result of a clogged filter or of an air leak in the fuel system. If the device does not prime or does not hold the idle run, or air bubbles are visible through the check glass, first of all check the cover by means of the T-handle and vent it, if it had not been closed properly. Then check all connections and lines and make sure that no fuel line is clogged with contaminants. If the fuel tank is equipped with an incorporated filter, check for its possible clogging. If the problem persists and the filter element is new, address to Dealer.
The separators have to be checked at regular intervals as suggested by manufacturer, so as not to impair the engines operation.